Fire Resisting Cable |
||||||||||
Fire Resisting Cables
300/500V SR Insulated, LSZH Sheathed, Screened Power Cables to BS 7629-1 (2-4 Cores & Multcore)
FFX200 05SOZ1-U/R PH30/PH60 (CU/SR/OSCR/LSZH 300/500V Class 1/2)
APPLICATION
The cables are primarily intended for use in the following applications:
BS 5266-1 for emergency lighting of premises.
BS 5839-1 for fire detection and fire alarm systems in and around building.
BS 5839-8 for voice alarm systems.
BS 5839-9 for emergency voice communication systems.
STANDARDS
Basic design to BS 7629-1:2015
FIRE PERFORMANCE
Circuit Integrity | BS 6387; BS EN50200 |
---|---|
Flame Retardance (single vertical wire or cable test) |
IEC 60332-1-2; EN 60332-1-2 |
Reduced fire Propagation (Vertically-mounted bundled wires & cables test) |
IEC 60332-3-24; EN 60332-3-24 |
Halogen free |
IEC 60754-1; EN 50267-2-1 |
No corrosive Gas emission |
IEC 60754-2; EN 50267-2-2 |
Minimum smoke emission |
IEC 61034-2; EN 61034-2 |
VOLTAGE RATING
300/500V
CABLE CONSTRUCTION
Conductor : Copper conductor according to BS EN 60228 class 1/2.
Insulation : Fire resistant special ceramized silicone rubber compound type EI 2 as per BS EN 50363-1.
Screened : One or more metallic or laminated metallic tape(s) shall be applied, either longitudinally or helically or
a combination of both, with the metallic element in contact with the uninsulated circuit protective conductor or
drain wire.
Circuit Protective Conductor : Uninsulated tinned copper conductor of the same section and class as the
insulated conductors in the two,three and four cores cables.
Sheath : Extruded LSZH type LTS 3 according to BS 7655-6.1.
Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties
can be offered as option.
COLOUR CODE
Insulation Colour :
Number of cores |
Core colours or numbering |
---|---|
2 cores+uninsulated circuit protective conductor |
Brown, Blue or Brown, Brown |
3 cores+uninsulated circuit protective conductor |
Brown, Black, Grey |
4 cores+uninsulated circuit protective conductor |
Brown, Blue, Black, Grey |
7, 12 and19 cores+uninsulated drain wire |
Numbers 1, 2, 3, 4, 5, 6, 7 and upwards or, for identification by colour, an identical colour(excluding brown and black),except for two adjacent cores in each layer distinctively coloured brown and black. |
Sheath Colour : Colours upon request.
PHYSICAL AND THERMAL PROPERTIES
Maximum temperature range during operation : 60°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius : 6 x Overall Diameter
CONSTRUCTION PARAMETERS
Conductor |
FFX200 05SOZ1-U/R PH30/PH60 |
|||||
---|---|---|---|---|---|---|
No. of Cores × Cross-sectional Area |
Conductor Class |
Nominal Insulation Thickness |
CPC Nominal Cross-sectional Area |
Nominal Sheath Thickness |
Approx. Overall Diameter |
Approx. Weight |
no.×mm² |
|
mm |
mm² |
mm |
mm |
kg/km |
2 cores |
||||||
2x1.0 |
1/2 |
0.6 |
1.0 |
0.9 |
8.0 |
78 |
2x1.5 |
1/2 |
0.7 |
1.5 |
0.9 |
8.5 |
103 |
2x2.5 |
1/2 |
0.8 |
2.5 |
1.0 |
10.5 |
150 |
2x4.0 |
1/2 |
0.8 |
4.0 |
1.1 |
12.5 |
212 |
3 cores |
||||||
3x1.5 |
1/2 |
0.7 |
1.5 |
0.9 |
9.5 |
130 |
3x2.5 |
1/2 |
0.8 |
2.5 |
1.0 |
11.5 |
191 |
3x4.0 |
1/2 |
0.8 |
4.0 |
1.1 |
13.5 |
273 |
4 cores |
||||||
4x1.5 |
1/2 |
0.7 |
1.5 |
1.0 |
10.5 |
165 |
4x2.5 |
1/2 |
0.8 |
2.5 |
1.1 |
12.0 |
242 |
4x4.0 |
1/2 |
0.8 |
4.0 |
1.2 |
15.0 |
344 |
7 cores |
||||||
7x1.5 |
1/2 |
0.7 |
0.5 |
1.1 |
12.5 |
257 |
7x2.5 |
1/2 |
0.8 |
0.5 |
1.2 |
15.0 |
568 |
12 cores |
||||||
12x1.5 |
1/2 |
0.7 |
0.5 |
1.2 |
16.0 |
414 |
12x2.5 |
1/2 |
0.8 |
0.5 |
1.4 |
20.0 |
886 |
19 cores |
||||||
19x1.5 |
1/2 |
0.7 |
0.5 |
1.3 |
19.0 |
617 |
ELECTRICAL PROPERTIES
Conductor operating temperature : 70°C
Ambient temperature : 30°C
Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D2A
Conductor cross-sectional area |
Ref. Method A (enclosed in conduit in thermally insulating wall etc) |
Ref. Method B (enclosed in conduit on a wall or in trunking etc) |
Ref. Method C (clipped direct) |
Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical) |
||||
1 two-core cable*, single-phase a.c. or d.c. |
1 three-core or 1 four-core cable*, three-phase a.c. |
1 two-core cable*, singlephase a.c. or d.c. |
1 three-core or 1 four-core cable*, three-phase a.c. |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-core or 1 four-core cable*, three-phase a.c. |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-core or 1 four-core cable*, three-phase a.c. |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
mm² |
A |
A |
A |
A |
A |
A |
A |
A |
1.0 |
11 |
10 |
13 |
11.5 |
15 |
13.5 |
17 |
14.5 |
1.5 |
14 |
13 |
16.5 |
15 |
19.5 |
17.5 |
22 |
18.5 |
2.5 |
18.5 |
17.5 |
23 |
20 |
27 |
24 |
30 |
25 |
4 |
25 |
23 |
30 |
27 |
36 |
32 |
40 |
34 |
Note: *With or without a protective conductor.
Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D2B
Conductor cross-sectional area |
Two-core cable d.c. |
Two-core cable single-phase a.c. |
Three- or four-core cable, three-phase a.c. |
---|---|---|---|
1 |
2 |
3 |
4 |
mm² |
mV/A/m |
mV/A/m |
mV/A/m |
1.0 |
44 |
44 |
38 |
1.5 |
29 |
29 |
25 |
2.5 |
18 |
18 |
15 |
4 |
11 |
11 |
9.5 |